Compressor — R290 compressor — 13.6 kW cooling, 4.55 kW input, COP 2.99 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZH11KCU-TF5 (R290 scroll, 60 Hz, HP) |
| Refrigerant | R290 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 2.8 K |
| Cooling capacity @ 7.2/54.4 °C | 13.60 kW |
| Input power @ 7.2/54.4 °C | 4.55 kW |
| COP @ 7.2/54.4 °C | 2.99 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 2.8 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 20 | 4.81 | 2.34 | 2.05 |
| -30 / 40 | 3.79 | 3.08 | 1.23 |
| -20 / 20 | 7.45 | 2.43 | 3.07 |
| -20 / 40 | 6.01 | 3.28 | 1.83 |
| -10 / 20 | 11.11 | 2.54 | 4.38 |
| -10 / 40 | 9.06 | 3.42 | 2.65 |
| -10 / 70 | 5.64 | 5.21 | 1.08 |
| 10 / 40 | 18.45 | 3.66 | 5.04 |
| 10 / 70 | 12.09 | 5.87 | 2.06 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZH11KCU-TF5 (R290 scroll, 50 Hz, HP) | R290 |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.