Compressor — R410A compressor — 17.6 kW cooling, 6.64 kW input, COP 2.65 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZPS83KCE-TFD (R410A scroll, 50 Hz, AC) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 17.61 kW |
| Input power @ 7.2/54.4 °C | 6.64 kW |
| COP @ 7.2/54.4 °C | 2.65 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 8-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 10 | 7.15 | 2.32 | 3.08 |
| -30 / 30 | 5.61 | 3.68 | 1.53 |
| -20 / 10 | 11.12 | 2.39 | 4.65 |
| -20 / 30 | 9.26 | 3.77 | 2.46 |
| 0 / 30 | 20.88 | 3.72 | 5.62 |
| 0 / 60 | 13.80 | 7.63 | 1.81 |
| 20 / 60 | 28.09 | 7.53 | 3.73 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZPS83KCE-TFD (R410A scroll, 60 Hz, AC) | R410A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.