Compressor — R410A compressor — 23.0 kW cooling, 8.28 kW input, COP 2.78 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZPS91KCE-TFD (R410A scroll, 60 Hz, AC) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 23.04 kW |
| Input power @ 7.2/54.4 °C | 8.28 kW |
| COP @ 7.2/54.4 °C | 2.78 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 8-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 10 | 9.84 | 2.79 | 3.53 |
| -30 / 30 | 7.35 | 4.70 | 1.56 |
| -20 / 10 | 14.85 | 2.90 | 5.12 |
| -20 / 30 | 11.99 | 4.86 | 2.47 |
| 0 / 30 | 26.73 | 4.93 | 5.42 |
| 0 / 60 | 18.20 | 9.46 | 1.92 |
| 20 / 60 | 36.76 | 9.38 | 3.92 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZPS91KCE-TFD (R410A scroll, 50 Hz, AC) | R410A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.