Copeland ZR42K5E-TFD (R22 scroll, 50 Hz, AC)

Compressor — R22 compressor — 9.2 kW cooling, 3.26 kW input, COP 2.81 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZR42K5E-TFD (R22 scroll, 50 Hz, AC)
RefrigerantR22
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C9.16 kW
Input power @ 7.2/54.4 °C3.26 kW
COP @ 7.2/54.4 °C2.81

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 304.171.882.22
-20 / 403.252.441.33
-10 / 306.821.833.73
-10 / 405.942.352.52
0 / 3010.071.815.56
0 / 409.142.293.99
0 / 606.283.921.60
10 / 3014.181.827.79
10 / 4013.132.255.83
10 / 6010.073.722.71

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZR42K5E-TFD (R22 scroll, 60 Hz, AC)R22
compressorsCopeland ZR42K5E-PFJ (R407C scroll, 50 Hz, AC)R407C
compressorsCopeland ZR42K5E-PFJ (R407C scroll, 60 Hz, AC)R407C

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy