Copeland ZR48K5E-TFD (R22 scroll, 50 Hz, AC)

Compressor — R22 compressor — 10.7 kW cooling, 3.42 kW input, COP 3.12 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZR48K5E-TFD (R22 scroll, 50 Hz, AC)
RefrigerantR22
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C10.68 kW
Input power @ 7.2/54.4 °C3.42 kW
COP @ 7.2/54.4 °C3.12

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 305.032.102.40
-20 / 404.482.641.70
-10 / 307.902.063.84
-10 / 407.082.562.76
0 / 3011.502.035.67
0 / 4010.562.494.24
0 / 607.834.081.92
10 / 3015.692.027.78
10 / 4014.782.446.05
10 / 6011.813.883.04

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZR48K5E-TFD (R22 scroll, 60 Hz, AC)R22
compressorsCopeland ZR48K5E-PFJ (R407C scroll, 50 Hz, AC)R407C
compressorsCopeland ZR48K5E-TFD (R407C scroll, 60 Hz, AC)R407C

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy