Compressor — R134a compressor — 14.6 kW cooling, 4.75 kW input, COP 3.06 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZR81KTE-TF5 (R134A scroll, 60 Hz, AC) |
| Refrigerant | R134a |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 14.55 kW |
| Input power @ 7.2/54.4 °C | 4.75 kW |
| COP @ 7.2/54.4 °C | 3.06 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 6.40 | 2.65 | 2.42 |
| -20 / 40 | 5.70 | 3.26 | 1.75 |
| -10 / 30 | 10.10 | 2.77 | 3.65 |
| -10 / 40 | 9.05 | 3.39 | 2.67 |
| 0 / 30 | 15.44 | 2.85 | 5.42 |
| 0 / 40 | 13.96 | 3.48 | 4.01 |
| 0 / 60 | 11.10 | 5.25 | 2.11 |
| 10 / 30 | 22.70 | 2.95 | 7.70 |
| 10 / 40 | 20.72 | 3.59 | 5.77 |
| 10 / 60 | 16.69 | 5.35 | 3.12 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZR81KTE-TF5 (R134A scroll, 50 Hz, AC) | R134a |
| compressors | Copeland ZR81KTE-TF5 (R22 scroll, 50 Hz, AC) | R22 |
| compressors | Copeland ZR81KTE-TF5 (R22 scroll, 60 Hz, AC) | R22 |
| compressors | Copeland ZR81KTE-TFD (R407C scroll, 50 Hz, AC) | R407C |
| compressors | Copeland ZR81KTE-TFD (R407C scroll, 60 Hz, AC) | R407C |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.