Copeland ZRH116KTE-TFD (R134A scroll, 50 Hz, AC)

Compressor — R134a compressor — 17.3 kW cooling, 6.24 kW input, COP 2.77 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZRH116KTE-TFD (R134A scroll, 50 Hz, AC)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C17.27 kW
Input power @ 7.2/54.4 °C6.24 kW
COP @ 7.2/54.4 °C2.77

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 3011.503.183.62
-20 / 409.673.702.61
-10 / 3013.353.563.75
-10 / 4011.674.342.69
0 / 3019.013.595.30
0 / 4017.144.483.82
0 / 6012.297.121.73
10 / 3027.853.667.61
10 / 4025.474.545.61
10 / 6019.417.102.74

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZRH116KTE-TFD (R134A scroll, 60 Hz, AC)R134a
compressorsCopeland ZRH116KTE-TFD (R407C scroll, 50 Hz, AC)R407C
compressorsCopeland ZRH116KTE-TF7 (R407C scroll, 60 Hz, AC)R407C

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy