Compressor — R134a compressor — 9.0 kW cooling, 3.14 kW input, COP 2.88 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZRH49KJE-TF7 (R134A scroll, 60 Hz, HT) |
| Refrigerant | R134a |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 9.03 kW |
| Input power @ 7.2/54.4 °C | 3.14 kW |
| COP @ 7.2/54.4 °C | 2.88 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 5.65 | 1.91 | 2.96 |
| -10 / 50 | 4.46 | 2.55 | 1.75 |
| 0 / 30 | 8.76 | 2.07 | 4.24 |
| 0 / 50 | 7.10 | 2.78 | 2.55 |
| 0 / 70 | 4.94 | 3.77 | 1.31 |
| 10 / 30 | 12.88 | 2.25 | 5.72 |
| 10 / 50 | 10.71 | 3.00 | 3.57 |
| 10 / 70 | 7.76 | 4.08 | 1.90 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.