Compressor — R407C compressor — 15.3 kW cooling, 5.40 kW input, COP 2.84 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZRH72KJE-TFD (R407C scroll, 50 Hz, HT) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 18.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 15.35 kW |
| Input power @ 7.2/54.4 °C | 5.40 kW |
| COP @ 7.2/54.4 °C | 2.84 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 18.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -12 to 13 °C, condensing 21 to 66 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 10.72 | 2.97 | 3.61 |
| -10 / 40 | 9.65 | 3.56 | 2.71 |
| -10 / 60 | 7.13 | 5.40 | 1.32 |
| 0 / 30 | 15.86 | 3.36 | 4.72 |
| 0 / 40 | 14.34 | 3.96 | 3.62 |
| 0 / 60 | 10.67 | 5.85 | 1.83 |
| 10 / 30 | 22.87 | 3.71 | 6.16 |
| 10 / 40 | 20.81 | 4.28 | 4.86 |
| 10 / 60 | 15.80 | 6.11 | 2.58 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZRH72KJE-TFD (R134A scroll, 50 Hz, HT) | R134a |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.