Compressor — R134a compressor — 10.9 kW cooling, 3.57 kW input, COP 3.05 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZRH72KJE-TFD (R134A scroll, 50 Hz, HT) |
| Refrigerant | R134a |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 10.88 kW |
| Input power @ 7.2/54.4 °C | 3.57 kW |
| COP @ 7.2/54.4 °C | 3.05 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 7.04 | 2.14 | 3.29 |
| -10 / 50 | 5.57 | 2.82 | 1.98 |
| 0 / 30 | 10.81 | 2.41 | 4.48 |
| 0 / 50 | 8.68 | 3.13 | 2.77 |
| 0 / 70 | 6.75 | 4.43 | 1.52 |
| 10 / 30 | 15.65 | 2.76 | 5.67 |
| 10 / 50 | 12.70 | 3.40 | 3.73 |
| 10 / 70 | 10.03 | 4.87 | 2.06 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZRH72KJE-TFD (R407C scroll, 50 Hz, HT) | R407C |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.