Catalog · Copeland

Copeland ZS19K4E-TF5 (R134A scroll, 50 Hz, EM)

Compressor — R134a compressor — 4.4 kW cooling, 1.59 kW input, COP 2.77 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZS19K4E-TF5 (R134A scroll, 50 Hz, EM)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.6 / 0.0 K
Cooling capacity @ 7.2/54.4 °C4.40 kW
Input power @ 7.2/54.4 °C1.59 kW
COP @ 7.2/54.4 °C2.77

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 301.170.771.52
-30 / 401.070.901.18
-20 / 301.890.902.10
-20 / 401.721.071.61
-10 / 302.980.963.11
-10 / 402.701.162.32
-10 / 602.111.621.30
0 / 304.530.974.66
0 / 404.101.203.41
0 / 603.191.731.85

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZS19K4E-TF5 (R134A scroll, 60 Hz, EM)R134a
compressorsCopeland ZS19K4E-PFV (R404A scroll, 50 Hz, EM)R404A
compressorsCopeland ZS19K4E-PFV (R404A scroll, 60 Hz, EM)R404A
compressorsCopeland ZS19K4E-TF5 (R507 scroll, 50 Hz, EM)R507
compressorsCopeland ZS19K4E-TF5 (R507 scroll, 60 Hz, EM)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy