Compressor — R134a compressor — 6.0 kW cooling, 2.16 kW input, COP 2.79 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZS26K4E-TF5 (R134A scroll, 50 Hz, EM) |
| Refrigerant | R134a |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 30.6 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 6.04 kW |
| Input power @ 7.2/54.4 °C | 2.16 kW |
| COP @ 7.2/54.4 °C | 2.79 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.6 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 30 | 1.64 | 1.05 | 1.56 |
| -30 / 40 | 1.49 | 1.23 | 1.22 |
| -20 / 30 | 2.64 | 1.20 | 2.19 |
| -20 / 40 | 2.40 | 1.44 | 1.67 |
| -10 / 30 | 4.13 | 1.29 | 3.20 |
| -10 / 40 | 3.75 | 1.57 | 2.39 |
| -10 / 60 | 2.94 | 2.20 | 1.34 |
| 0 / 30 | 6.22 | 1.32 | 4.72 |
| 0 / 40 | 5.65 | 1.63 | 3.46 |
| 0 / 60 | 4.41 | 2.34 | 1.89 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZS26K4E-TF5 (R134A scroll, 60 Hz, EM) | R134a |
| compressors | Copeland ZS26K4E-TF5 (R404A scroll, 50 Hz, EM) | R404A |
| compressors | Copeland ZS26K4E-TF5 (R404A scroll, 60 Hz, EM) | R404A |
| compressors | Copeland ZS26K4E-TF5 (R507 scroll, 50 Hz, EM) | R507 |
| compressors | Copeland ZS26K4E-TF5 (R507 scroll, 60 Hz, EM) | R507 |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |