Catalog · Copeland

Copeland ZS30K4E-TF5 (R134A scroll, 50 Hz, HT)

Compressor — R134a compressor — 7.3 kW cooling, 2.52 kW input, COP 2.88 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZS30K4E-TF5 (R134A scroll, 50 Hz, HT)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool26.4 / 0.0 K
Cooling capacity @ 7.2/54.4 °C7.27 kW
Input power @ 7.2/54.4 °C2.52 kW
COP @ 7.2/54.4 °C2.88

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 26.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -23 to 7 °C, condensing 21 to 60 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 303.161.382.30
-20 / 402.881.651.75
-20 / 602.282.261.01
-10 / 304.941.483.35
-10 / 404.491.802.50
-10 / 603.512.521.39
0 / 307.421.534.86
0 / 406.751.893.58
0 / 605.272.701.95

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZS30K4E-TF5 (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland ZS30K4E-TF5 (R404A scroll, 50 Hz, EM)R404A
compressorsCopeland ZS30K4E-TF5 (R404A scroll, 60 Hz, EM)R404A
compressorsCopeland ZS30K4E-TF5 (R507 scroll, 50 Hz, EM)R507
compressorsCopeland ZS30K4E-TF5 (R507 scroll, 60 Hz, EM)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy