Compressor — R407C compressor — 15.5 kW cooling, 5.20 kW input, COP 2.99 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZX45KCE-TFD (R407C scroll, 50 Hz, HT) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 18.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 15.54 kW |
| Input power @ 7.2/54.4 °C | 5.20 kW |
| COP @ 7.2/54.4 °C | 2.99 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 18.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -12 to 13 °C, condensing 21 to 66 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 10.77 | 2.88 | 3.74 |
| -10 / 40 | 9.57 | 3.65 | 2.62 |
| -10 / 60 | 6.86 | 6.02 | 1.14 |
| 0 / 30 | 15.93 | 2.94 | 5.43 |
| 0 / 40 | 14.41 | 3.70 | 3.89 |
| 0 / 60 | 10.75 | 5.96 | 1.80 |
| 10 / 30 | 22.56 | 2.96 | 7.63 |
| 10 / 40 | 20.70 | 3.74 | 5.54 |
| 10 / 60 | 16.09 | 5.95 | 2.71 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZX45KCE-TFD (R407A scroll, 50 Hz, MT) | R407A |
| compressors | Copeland ZX45KCE-TFD (R407A scroll, 60 Hz, HT) | R407A |
| compressors | Copeland ZX45KCE-TFD (R407C scroll, 60 Hz, HT) | R407C |
| compressors | Copeland ZX45KCE-TFD (R407F scroll, 50 Hz, MT) | R407F |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.