Compressor — R407C compressor — 19.0 kW cooling, 6.25 kW input, COP 3.04 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZX45KCE-TFD (R407C scroll, 60 Hz, HT) |
| Refrigerant | R407C |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 18.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 19.02 kW |
| Input power @ 7.2/54.4 °C | 6.25 kW |
| COP @ 7.2/54.4 °C | 3.04 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 18.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -12 to 13 °C, condensing 21 to 66 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 13.29 | 3.47 | 3.82 |
| -10 / 40 | 11.81 | 4.37 | 2.70 |
| -10 / 60 | 8.74 | 7.06 | 1.24 |
| 0 / 30 | 19.62 | 3.59 | 5.46 |
| 0 / 40 | 17.80 | 4.47 | 3.98 |
| 0 / 60 | 13.26 | 7.09 | 1.87 |
| 10 / 30 | 27.31 | 3.65 | 7.47 |
| 10 / 40 | 25.27 | 4.55 | 5.55 |
| 10 / 60 | 19.54 | 7.14 | 2.74 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZX45KCE-TFD (R407A scroll, 50 Hz, MT) | R407A |
| compressors | Copeland ZX45KCE-TFD (R407A scroll, 60 Hz, HT) | R407A |
| compressors | Copeland ZX45KCE-TFD (R407C scroll, 50 Hz, HT) | R407C |
| compressors | Copeland ZX45KCE-TFD (R407F scroll, 50 Hz, MT) | R407F |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.