Catalog · Embraco

Embraco NT2192GKAV (R404A hermetic, LBP, EN12900, 50 Hz)

Compressor — R404A compressor — 2.6 kW cooling, 1.37 kW input, COP 1.93 at the AHRI 7.2/54.4 °C rating point.

A Embraco listing, from the manufacturer's published data.

Published specification

ModelEmbraco NT2192GKAV (R404A hermetic, LBP, EN12900, 50 Hz)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool45.0 / 0.0 K
Cooling capacity @ 7.2/54.4 °C2.63 kW
Input power @ 7.2/54.4 °C1.37 kW
COP @ 7.2/54.4 °C1.93

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 45.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-40 / 200.610.401.53
-40 / 300.510.431.19
-30 / 201.070.512.09
-30 / 300.910.571.60
-30 / 500.590.610.96
-20 / 201.730.612.86
-20 / 301.500.712.11
-20 / 501.000.821.23
-10 / 202.630.654.04
-10 / 302.280.812.81
-10 / 501.561.021.53

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

How the model reads against this maker's data

Embraco hermetic and variable-capacity compressor maps, fitted from the maker's published tables1,283 maps from 815 models (R134a 518, R600a 315, R290 285, R404A 141, R22 11, R1234yf 10, R422D 2, R502 1); 178 variable-capacity models with a table per speedfitted at the order each table's levels determine (three condensing levels: quadratic in tc), the tables are reproduced at a median RMS of 0.08 % (p90 0.20 %); every map reads the standard's own rating point within 0.08 % at the median and 0.4 % at the ninetieth percentile; every carried flow set closes the identity once the rating's own return-gas and liquid temperatures are read off the node (ASHRAE rates with the liquid at 32.2 °C, 22 K under the condenser). 72 tables withheld and listed by reason: blend groups published as one table, variable-capacity models with fewer than three speeds tabulated, three with a COP under 0.5 at the rating point, three duplicates

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy