Compressor — R404A compressor — 3.0 kW cooling, 1.73 kW input, COP 1.72 at the AHRI 7.2/54.4 °C rating point.
A Embraco listing, from the manufacturer's published data.
| Model | Embraco NT2210GK (R404A hermetic, LBP, EN12900, 50 Hz) |
| Refrigerant | R404A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 45.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 2.98 kW |
| Input power @ 7.2/54.4 °C | 1.73 kW |
| COP @ 7.2/54.4 °C | 1.72 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 45.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 20 | 0.73 | 0.50 | 1.46 |
| -40 / 30 | 0.60 | 0.54 | 1.12 |
| -30 / 20 | 1.27 | 0.63 | 2.02 |
| -30 / 30 | 1.08 | 0.70 | 1.54 |
| -30 / 50 | 0.72 | 0.78 | 0.93 |
| -20 / 20 | 2.02 | 0.73 | 2.75 |
| -20 / 30 | 1.75 | 0.86 | 2.03 |
| -20 / 50 | 1.21 | 1.02 | 1.18 |
| -10 / 20 | 2.97 | 0.79 | 3.76 |
| -10 / 30 | 2.60 | 0.99 | 2.62 |
| -10 / 50 | 1.84 | 1.28 | 1.44 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Embraco hermetic and variable-capacity compressor maps, fitted from the maker's published tables | 1,283 maps from 815 models (R134a 518, R600a 315, R290 285, R404A 141, R22 11, R1234yf 10, R422D 2, R502 1); 178 variable-capacity models with a table per speed | fitted at the order each table's levels determine (three condensing levels: quadratic in tc), the tables are reproduced at a median RMS of 0.08 % (p90 0.20 %); every map reads the standard's own rating point within 0.08 % at the median and 0.4 % at the ninetieth percentile; every carried flow set closes the identity once the rating's own return-gas and liquid temperatures are read off the node (ASHRAE rates with the liquid at 32.2 °C, 22 K under the condenser). 72 tables withheld and listed by reason: blend groups published as one table, variable-capacity models with fewer than three speeds tabulated, three with a COP under 0.5 at the rating point, three duplicates |