Embraco NTU6234GKV (R404A hermetic, MBP, EN12900, 60 Hz)

Compressor — R404A compressor — 3.9 kW cooling, 1.75 kW input, COP 2.24 at the AHRI 7.2/54.4 °C rating point.

A Embraco listing, from the manufacturer's published data.

Published specification

ModelEmbraco NTU6234GKV (R404A hermetic, MBP, EN12900, 60 Hz)
RefrigerantR404A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool25.0 / 0.0 K
Cooling capacity @ 7.2/54.4 °C3.93 kW
Input power @ 7.2/54.4 °C1.75 kW
COP @ 7.2/54.4 °C2.24

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 25.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 202.530.852.98
-20 / 302.200.952.31
-10 / 203.730.894.20
-10 / 303.281.083.05
-10 / 502.281.311.74
0 / 205.400.816.63
0 / 304.751.124.24
0 / 503.351.542.18
10 / 207.590.5713.39
10 / 306.701.036.51
10 / 504.781.702.81

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsEmbraco NTU6234GKV (R404A hermetic, MBP, EN12900, 50 Hz)R404A

How the model reads against this maker's data

Embraco hermetic and variable-capacity compressor maps, fitted from the maker's published tables1,283 maps from 815 models (R134a 518, R600a 315, R290 285, R404A 141, R22 11, R1234yf 10, R422D 2, R502 1); 178 variable-capacity models with a table per speedfitted at the order each table's levels determine (three condensing levels: quadratic in tc), the tables are reproduced at a median RMS of 0.08 % (p90 0.20 %); every map reads the standard's own rating point within 0.08 % at the median and 0.4 % at the ninetieth percentile; every carried flow set closes the identity once the rating's own return-gas and liquid temperatures are read off the node (ASHRAE rates with the liquid at 32.2 °C, 22 K under the condenser). 72 tables withheld and listed by reason: blend groups published as one table, variable-capacity models with fewer than three speeds tabulated, three with a COP under 0.5 at the rating point, three duplicates

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy