Compressor — R22 compressor — 19.3 kW cooling, 6.82 kW input, COP 2.82 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YF41A7G-Q100 (R22 low-temperature freezing scroll, 60 Hz, 220 V 3P) |
| Refrigerant | R22 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 38.3 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 19.26 kW |
| Input power @ 7.2/54.4 °C | 6.82 kW |
| COP @ 7.2/54.4 °C | 2.82 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 38.3 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -40 / 30 | 3.94 | 2.61 | 1.51 |
| -40 / 40 | 3.56 | 3.28 | 1.09 |
| -30 / 30 | 6.17 | 2.93 | 2.10 |
| -30 / 40 | 5.68 | 3.58 | 1.59 |
| -20 / 30 | 9.21 | 3.30 | 2.79 |
| -20 / 40 | 8.58 | 3.94 | 2.18 |
| 0 / 30 | 18.42 | 4.19 | 4.40 |
| 0 / 40 | 17.37 | 4.88 | 3.56 |
| 0 / 60 | 14.41 | 7.05 | 2.05 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Invotech YF41A7G-V100 (R22 low-temperature freezing scroll, 60 Hz, 220 V 3P) | R22 |
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.