Compressor — R410A compressor — 12.9 kW cooling, 4.22 kW input, COP 3.06 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YH128C6-100 (R410A air-conditioning scroll, 50 Hz, 220 V 3P) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 12.91 kW |
| Input power @ 7.2/54.4 °C | 4.22 kW |
| COP @ 7.2/54.4 °C | 3.06 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 6.09 | 2.49 | 2.45 |
| -20 / 40 | 5.30 | 3.18 | 1.66 |
| -10 / 30 | 9.25 | 2.45 | 3.78 |
| -10 / 40 | 8.27 | 3.10 | 2.67 |
| 0 / 30 | 13.33 | 2.43 | 5.49 |
| 0 / 40 | 11.98 | 3.03 | 3.95 |
| 0 / 60 | 8.99 | 4.94 | 1.82 |
| 10 / 30 | 18.90 | 2.47 | 7.65 |
| 10 / 40 | 16.97 | 3.03 | 5.61 |
| 10 / 60 | 13.04 | 4.85 | 2.69 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.