Catalog · Invotech · YH

Invotech YH266A1-100 (R22 air-conditioning scroll, 60 Hz, 460 V 3P)

Compressor — R22 compressor — 32.1 kW cooling, 9.29 kW input, COP 3.45 at the AHRI 7.2/54.4 °C rating point.

An Invotech listing, from the manufacturer's published data.

Units: SI · US customary

Published specification

ModelInvotech YH266A1-100 (R22 air-conditioning scroll, 60 Hz, 460 V 3P)
RefrigerantR22
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 8.3 K
Cooling capacity @ 7.2/54.4 °C32.05 kW
Input power @ 7.2/54.4 °C9.29 kW
COP @ 7.2/54.4 °C3.45

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
7.2 / 54.432.059.293.45
-20 / 4511.727.281.61
-5 / 4522.637.543.00
5 / 4532.747.634.29

The rating point and three conditions across the published envelope. The whole map — every condition, the envelope and the curves — is in the builder: open this machine in the app. It solves any point inside the envelope, and warns past it.

Open this compressor in the app — the compressor-map tab, with its rating at any condition, its envelope, capacity and power lines and curves plotted, and the refrigerant's pressure–temperature chart a click away; or open the builder and pick it from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

CompressorInvotech YH266A1-100 (R22 air-conditioning scroll, 50 Hz, 380 V 3P)R22

All 292 Invotech YH models

How the model reads against this maker's data

Invotech scroll maps read from the Invowin selection tool's own database1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz)nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.