Compressor — R410A compressor — 11.4 kW cooling, 3.82 kW input, COP 3.00 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YH95C7-100 (R410A air-conditioning scroll, 60 Hz, 220 V 3P) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 11.44 kW |
| Input power @ 7.2/54.4 °C | 3.82 kW |
| COP @ 7.2/54.4 °C | 3.00 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 5.40 | 2.25 | 2.40 |
| -20 / 40 | 4.70 | 2.88 | 1.63 |
| -10 / 30 | 8.19 | 2.21 | 3.71 |
| -10 / 40 | 7.33 | 2.80 | 2.62 |
| 0 / 30 | 11.82 | 2.19 | 5.39 |
| 0 / 40 | 10.61 | 2.74 | 3.87 |
| 0 / 60 | 7.97 | 4.46 | 1.79 |
| 10 / 30 | 16.75 | 2.24 | 7.50 |
| 10 / 40 | 15.04 | 2.74 | 5.50 |
| 10 / 60 | 11.56 | 4.39 | 2.63 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.