Invotech YSF90A1G-V100 (R22 low-temperature freezing scroll, 50 Hz, 380 V 3P)
Compressor — R22 compressor — 32.4 kW cooling, 11.99 kW input, COP 2.70 at the AHRI 7.2/54.4 °C rating point.
An Invotech listing, from the manufacturer's published data.
Units: SI · US customary
Published specification
| Model | Invotech YSF90A1G-V100 (R22 low-temperature freezing scroll, 50 Hz, 380 V 3P) |
| Refrigerant | R22 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 32.4 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 32.38 kW |
| Input power @ 7.2/54.4 °C | 11.99 kW |
| COP @ 7.2/54.4 °C | 2.70 |
The map across its envelope
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 32.4 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 7-sided polygon.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| 7.2 / 54.4 | 32.38 | 11.99 | 2.70 |
| -30 / 40 | 10.37 | 6.48 | 1.60 |
| -15 / 40 | 17.53 | 7.35 | 2.39 |
| 0 / 40 | 27.86 | 8.42 | 3.31 |
The rating point and three conditions across the published envelope. The whole map — every condition, the envelope and the curves — is in the builder: open this machine in the app. It solves any point inside the envelope, and warns past it.
Open this compressor in the app — the compressor-map tab, with its rating at any condition, its envelope, capacity and power lines and curves plotted, and the refrigerant's pressure–temperature chart a click away; or open the builder and pick it from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
How the model reads against this maker's data
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.