Compressor — R410A compressor — 10.9 kW cooling, 3.78 kW input, COP 2.88 at the AHRI 7.2/54.4 °C rating point.
A Invotech listing, from the manufacturer's published data.
| Model | Invotech YW75C8-100 (R410A heat-pump water heater scroll, 60 Hz, 575 V 3P) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 10.87 kW |
| Input power @ 7.2/54.4 °C | 3.78 kW |
| COP @ 7.2/54.4 °C | 2.88 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 20 | 5.78 | 1.77 | 3.27 |
| -20 / 40 | 4.58 | 2.56 | 1.79 |
| -10 / 20 | 8.71 | 1.85 | 4.72 |
| -10 / 40 | 7.06 | 2.67 | 2.64 |
| 0 / 20 | 12.43 | 2.05 | 6.06 |
| 0 / 40 | 10.33 | 2.77 | 3.73 |
| 0 / 60 | 7.65 | 4.05 | 1.89 |
| 10 / 40 | 14.46 | 2.99 | 4.84 |
| 10 / 60 | 10.89 | 4.30 | 2.53 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Invotech scroll maps read from the Invowin selection tool's own database | 1 103 maps (R22, R410A, R404A, R407C, R134a, R448A, R449A, R452A, R455A, R454C; 50 and 60 Hz) | nomenclature median +0.5 %, worst 5.1 %; the tool's SI cubics carried exactly, ×1000 and ÷3600; 990 flow sets close within 15 %, 113 whole low-temperature families sit at a flat 0.76–0.85 of Q/Δh and ship without their flow set, each recorded with its ratio |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.