Catalog · Tecumseh

Tecumseh AJ4511N-FZ3B (R513A hermetic, HBP, EN12900, 50 Hz)

Compressor — R513A compressor — 2.7 kW cooling, 1.25 kW input, COP 2.19 at the AHRI 7.2/54.4 °C rating point.

A Tecumseh listing, from the manufacturer's published data.

Published specification

ModelTecumseh AJ4511N-FZ3B (R513A hermetic, HBP, EN12900, 50 Hz)
RefrigerantR513A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool25.0 / 0.0 K
Cooling capacity @ 7.2/54.4 °C2.73 kW
Input power @ 7.2/54.4 °C1.25 kW
COP @ 7.2/54.4 °C2.19

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 25.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -25 to 15 °C, condensing 30 to 60 °C (a rectangle).

te / tc °CCapacity kWPower kWCOP
-20 / 301.270.622.05
-20 / 401.040.621.68
-20 / 600.520.511.03
-10 / 302.070.752.75
-10 / 401.760.802.20
-10 / 601.110.841.32
0 / 303.150.893.55
0 / 402.710.962.81
0 / 601.801.121.61
10 / 304.601.064.34
10 / 403.951.153.44
10 / 602.671.391.93

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsTecumseh AJ4511N-CZ3A (R1234yf hermetic, HBP, EN12900, 50 Hz)R1234yf
compressorsTecumseh AJ4511N-FZ3B (R1234yf hermetic, HBP, EN12900, 50 Hz)R1234yf
compressorsTecumseh AJ4511N-TZ1A (R1234yf hermetic, HBP, EN12900, 50 Hz)R1234yf
compressorsTecumseh AJ4511N-TZ1A (R1234yf hermetic, HBP, EN12900, 60 Hz)R1234yf
compressorsTecumseh AJ4511N-CZ3A (R1234yf hermetic, HBP, EN12900, 60 Hz)R1234yf
compressorsTecumseh AJ4511N-CZ3A (R134a hermetic, HBP, EN12900, 50 Hz)R134a
compressorsTecumseh AJ4511N-TZ1A (R134a hermetic, HBP, EN12900, 50 Hz)R134a
compressorsTecumseh AJ4511N-FZ3B (R134a hermetic, HBP, EN12900, 50 Hz)R134a
compressorsTecumseh AJ4511N-TZ1A (R134a hermetic, HBP, EN12900, 60 Hz)R134a
compressorsTecumseh AJ4511N-CZ3A (R134a hermetic, HBP, EN12900, 60 Hz)R134a
compressorsTecumseh AJ4511N-CZ3A (R513A hermetic, HBP, EN12900, 50 Hz)R513A
compressorsTecumseh AJ4511N-TZ1A (R513A hermetic, HBP, EN12900, 50 Hz)R513A

How the model reads against this maker's data

Tecumseh hermetic compressor maps, the maker's own coefficient sets864 maps from 297 models (R404A 324, R134a 178, R290 109, R22 97, R513A 89, R1234yf 53, R600a 10, R410A 4) at 93 application × refrigerant × frequency listingspower reads the selector's point within 0.95 % on every map (units and coefficient order, BTU/h sets scaled and Fahrenheit sets substituted exactly); 522 maps rate at their own basis and read the selector's capacity within 1 %; on the 342 the selector corrected from a liquid-temperature or return-gas basis to the regime, this solver's AHRI 540 §6 correction reproduces the selector's corrected capacity within +0.3 % on average (the raw polynomial sits +9.5 % over it), single maps ±11 % where a return-gas basis is carried as one reference superheat. 2 028 zeotrope rows (R448A, R449A, R452A, R454C, R455A, R407C) are withheld: Tecumseh publishes them on the glide's mid-point where AHRI 540 and this catalog rate on dew points

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy