Showing 97–113 of 113

Sigma SRK-W-8-CV3-2H-4CC panel radiator (wall mount, CV3-2H-4CC coil), per foot

Hydronic emitter rated per foot of active length: 0.519 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-8-CV3-3H-4CC panel radiator (wall mount, CV3-3H-4CC coil), per foot

Hydronic emitter rated per foot of active length: 0.610 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-8-CV3-4H-4CC panel radiator (wall mount, CV3-4H-4CC coil), per foot

Hydronic emitter rated per foot of active length: 0.646 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-8-E24-1R panel radiator (wall mount, E24 element, 1 row), per foot

Hydronic emitter rated per foot of active length: 0.288 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-8-E24-2R panel radiator (wall mount, E24 element, 2 rows), per foot

Hydronic emitter rated per foot of active length: 0.396 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-8-E24-3R panel radiator (wall mount, E24 element, 3 rows), per foot

Hydronic emitter rated per foot of active length: 0.456 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-9-CV2-2H-4CC panel radiator (wall mount, CV2-2H-4CC coil), per foot

Hydronic emitter rated per foot of active length: 0.340 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-9-CV2-3H-4CC panel radiator (wall mount, CV2-3H-4CC coil), per foot

Hydronic emitter rated per foot of active length: 0.399 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-9-CV2-4H-4CC panel radiator (wall mount, CV2-4H-4CC coil), per foot

Hydronic emitter rated per foot of active length: 0.429 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-9-CV2-F6 panel radiator (wall mount, CV2-F6 coil), per foot

Hydronic emitter rated per foot of active length: 0.236 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-9-CV3-2H-4CC panel radiator (wall mount, CV3-2H-4CC coil), per foot

Hydronic emitter rated per foot of active length: 0.535 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-9-CV3-3H-4CC panel radiator (wall mount, CV3-3H-4CC coil), per foot

Hydronic emitter rated per foot of active length: 0.629 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-9-CV3-4H-4CC panel radiator (wall mount, CV3-4H-4CC coil), per foot

Hydronic emitter rated per foot of active length: 0.666 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-9-E24-1R panel radiator (wall mount, E24 element, 1 row), per foot

Hydronic emitter rated per foot of active length: 0.297 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-9-E24-2R panel radiator (wall mount, E24 element, 2 rows), per foot

Hydronic emitter rated per foot of active length: 0.410 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

Sigma SRK-W-9-E24-3R panel radiator (wall mount, E24 element, 3 rows), per foot

Hydronic emitter rated per foot of active length: 0.473 kW at an excess of 52.8 K, exponent 1.3.

catalog
Radiator / emitter · NA

U.S. Boiler Baseray 9A cast-iron baseboard, per foot of active length (1 gpm)

Hydronic emitter rated per foot of active length: 0.122 kW at an excess of 63.9 K, exponent 1.238.

catalog
Radiator / emitter · NA
‹ Previous1…345