Compressors with AHRI 540 maps, coils with real geometry, fans, pumps, evaporative media, heaters, humidifiers, radiators, exchangers and recovery cores — the parts the builder models, published by the manufacturers themselves and selectable directly inside the builder, where each one solves on its own published figures.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 12,601–12,624 of 15,410

NameTypeManufacturerRatingMarketsOpen in the builder
Danfoss MLZ038T1A (R404A scroll, 60 Hz, MT) CatalogCompressorsDanfossR404A compressor — 15.4 kW cooling, 5.98 kW input, COP 2.57 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland ZF06KQE-TF5 (R407F scroll, 60 Hz, LL) CatalogCompressorsCopelandR407F compressor — 1.5 kW cooling, 1.31 kW input, COP 1.14 at -35/35 °C (evaporating/condensing), inside its published envelope.APACOpen in the builder
Danfoss MTZ080-4 (R404A hermetic reciprocating, 60 Hz, MT) CatalogCompressorsDanfossR404A compressor — 21.6 kW cooling, 10.06 kW input, COP 2.15 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland ZFH09KAE-TF5 (R507 scroll, 60 Hz, LT) CatalogCompressorsCopelandR507 compressor — 2.2 kW cooling, 1.87 kW input, COP 1.19 at -35/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Danfoss MLZ038T1A (R407C scroll, 60 Hz, MT) CatalogCompressorsDanfossR407C compressor — 16.8 kW cooling, 5.36 kW input, COP 3.14 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland ZP35LXE-TFD (R410A scroll, 60 Hz, AC) CatalogCompressorsCopelandR410A compressor — 10.1 kW cooling, 3.39 kW input, COP 2.99 at the AHRI 7.2/54.4 °C rating point.NAOpen in the builder
Danfoss MTZ080-4 (R407A hermetic reciprocating, 50 Hz, MT) CatalogCompressorsDanfossR407A compressor — 17.9 kW cooling, 7.16 kW input, COP 2.49 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland ZR250KCE-TED (R407C scroll, 50 Hz, AC) CatalogCompressorsCopelandR407C compressor — 58.5 kW cooling, 17.99 kW input, COP 3.25 at the AHRI 7.2/54.4 °C rating point.EU, APACOpen in the builder
Danfoss MLZ038T1A (R448A scroll, 60 Hz, MT) CatalogCompressorsDanfossR448A compressor — 16.1 kW cooling, 5.82 kW input, COP 2.77 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland ZS15KAE-TF5 (R507 scroll, 60 Hz, EM) CatalogCompressorsCopelandR507 compressor — 2.9 kW cooling, 1.57 kW input, COP 1.83 at -25/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Danfoss MTZ080-4 (R407A hermetic reciprocating, 60 Hz, MT) CatalogCompressorsDanfossR407A compressor — 21.4 kW cooling, 8.60 kW input, COP 2.49 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland ZW72KSE-TF7 (R134A scroll, 60 Hz, HE) CatalogCompressorsCopelandR134a compressor — 21.7 kW cooling, 4.78 kW input, COP 4.53 at the AHRI 7.2/54.4 °C rating point.APACOpen in the builder
Danfoss MLZ038T1A (R449A scroll, 60 Hz, MT) CatalogCompressorsDanfossR449A compressor — 16.1 kW cooling, 5.82 kW input, COP 2.77 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland CR47KQE-TFD (R407C hermetic recip, 60 Hz, AC) CatalogCompressorsCopelandR407C compressor — 12.9 kW cooling, 4.16 kW input, COP 3.10 at the AHRI 7.2/54.4 °C rating point.NAOpen in the builder
Danfoss MTZ080-4 (R407C hermetic reciprocating, 50 Hz, HT) CatalogCompressorsDanfossR407C compressor — 17.6 kW cooling, 6.83 kW input, COP 2.58 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland YB21K1E-TFD (R455A scroll, 60 Hz, MT) CatalogCompressorsCopelandR455A compressor — 6.2 kW cooling, 2.35 kW input, COP 2.62 at -15/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Danfoss MLZ038T1A (R452A scroll, 60 Hz, MT) CatalogCompressorsDanfossR452A compressor — 15.4 kW cooling, 6.05 kW input, COP 2.55 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland YBD31K1E-TFD (R513A scroll, 60 Hz, MT) CatalogCompressorsCopelandR513A compressor — 6.0 kW cooling, 2.27 kW input, COP 2.66 at -15/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Danfoss MTZ080-4 (R407C hermetic reciprocating, 60 Hz, A/C) CatalogCompressorsDanfossR407C compressor — 22.9 kW cooling, 8.24 kW input, COP 2.77 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland YF06KAE-TFD (R407C scroll, 60 Hz, LL) CatalogCompressorsCopelandR407C compressor — 1.2 kW cooling, 1.19 kW input, COP 1.05 at -35/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Danfoss MLZ038T1A (R513A scroll, 60 Hz, MT) CatalogCompressorsDanfossR513A compressor — 10.3 kW cooling, 3.89 kW input, COP 2.64 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland YFH08KAE-TF5 (R407F scroll, 60 Hz, LT) CatalogCompressorsCopelandR407F compressor — 1.8 kW cooling, 1.68 kW input, COP 1.09 at -35/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Danfoss MTZ080-4 (R407F hermetic reciprocating, 50 Hz, MT) CatalogCompressorsDanfossR407F compressor — 19.3 kW cooling, 7.57 kW input, COP 2.54 at the AHRI 7.2/54.4 °C rating point.Open in the builder
Copeland YS17KSE-TF5 (R454C scroll, 60 Hz, EM) CatalogCompressorsCopelandR454C compressor — 2.5 kW cooling, 1.64 kW input, COP 1.53 at -25/40 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
‹ Previous1…524525526527528…643Next ›

Refrigerant circuit

Heat exchangers and recovery

Fans and air movement

Pumps and hydronics

Heating and humidity

Evaporative cooling and heat rejection

Cooling towers — none listed yet

Complete machines — air handlers, rooftops, splits, chillers, fan coils, cooling towers — are systems: the systems directory

Publishing here

Manufacturers publish from the supplier portal, or bulk-import a whole range over MCP. How it works for component vendors Twelve manufacturers' ranges are already in the catalog from their published data — the brands, and how to claim one