Published components

Compressors with AHRI 540 maps, coils with real geometry, fans, pumps, evaporative media, heaters, humidifiers, radiators, exchangers and recovery cores — the parts the builder models, published by the manufacturers themselves and selectable directly inside the builder, where each one solves on its own published figures.

Suppliers 46Systems 3,474Components 15,410Accessories 3

Showing 14,953–14,976 of 15,410

NameTypeManufacturerRatingMarketsOpen in the builder
Copeland YF32KAE-TFD (R449A scroll, 60 Hz, LL) CatalogCompressorsCopelandR449A compressor — 9.5 kW cooling, 5.94 kW input, COP 1.60 at -35/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland ZB29KCE-TF5 (R407F scroll, 60 Hz, MT) CatalogCompressorsCopelandR407F compressor — 7.0 kW cooling, 2.88 kW input, COP 2.44 at -15/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland ZF15K4E-TF5 (R407F scroll, 60 Hz, LL) CatalogCompressorsCopelandR407F compressor — 5.1 kW cooling, 2.62 kW input, COP 1.93 at -30/25 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland YF32KAE-TFD (R454A scroll, 50 Hz, LL) CatalogCompressorsCopelandR454A compressor — 8.2 kW cooling, 6.13 kW input, COP 1.34 at -35/35 °C (evaporating/condensing), inside its published envelope.EU, APACOpen in the builder
Copeland ZB29KCE-TF5 (R448A scroll, 50 Hz, MT) CatalogCompressorsCopelandR448A compressor — 6.0 kW cooling, 2.46 kW input, COP 2.44 at -15/35 °C (evaporating/condensing), inside its published envelope.EU, APACOpen in the builder
Copeland ZF15K4E-TF5 (R448A scroll, 50 Hz, LL) CatalogCompressorsCopelandR448A compressor — 4.4 kW cooling, 2.24 kW input, COP 1.95 at -30/25 °C (evaporating/condensing), inside its published envelope.EU, APACOpen in the builder
Copeland YF32KAE-TFD (R454A scroll, 60 Hz, LL) CatalogCompressorsCopelandR454A compressor — 9.9 kW cooling, 7.35 kW input, COP 1.34 at -35/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland ZB29KCE-TF5 (R448A scroll, 60 Hz, MT) CatalogCompressorsCopelandR448A compressor — 7.2 kW cooling, 2.95 kW input, COP 2.44 at -15/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland ZF15K4E-TF5 (R448A scroll, 60 Hz, LL) CatalogCompressorsCopelandR448A compressor — 5.2 kW cooling, 2.69 kW input, COP 1.95 at -30/25 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland YF32KAE-TFD (R454C scroll, 50 Hz, ML) CatalogCompressorsCopelandR454C compressor — 17.6 kW cooling, 6.16 kW input, COP 2.85 at -15/30 °C (evaporating/condensing), inside its published envelope.EU, APACOpen in the builder
Copeland ZB29KCE-TF5 (R449A scroll, 50 Hz, MT) CatalogCompressorsCopelandR449A compressor — 6.0 kW cooling, 2.46 kW input, COP 2.44 at -15/35 °C (evaporating/condensing), inside its published envelope.EU, APACOpen in the builder
Copeland ZF15K4E-TF5 (R449A scroll, 50 Hz, LL) CatalogCompressorsCopelandR449A compressor — 4.4 kW cooling, 2.24 kW input, COP 1.95 at -30/25 °C (evaporating/condensing), inside its published envelope.EU, APACOpen in the builder
Copeland YF32KAE-TFD (R454C scroll, 60 Hz, LL) CatalogCompressorsCopelandR454C compressor — 8.4 kW cooling, 5.99 kW input, COP 1.39 at -35/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland ZB29KCE-TF5 (R449A scroll, 60 Hz, MT) CatalogCompressorsCopelandR449A compressor — 7.2 kW cooling, 2.95 kW input, COP 2.44 at -15/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland ZF15K4E-TF5 (R449A scroll, 60 Hz, LL) CatalogCompressorsCopelandR449A compressor — 5.2 kW cooling, 2.69 kW input, COP 1.95 at -30/25 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland YF32KAE-TFD (R455A scroll, 50 Hz, LL) CatalogCompressorsCopelandR455A compressor — 7.6 kW cooling, 5.32 kW input, COP 1.42 at -35/35 °C (evaporating/condensing), inside its published envelope.EU, APACOpen in the builder
Copeland ZB29KCE-TF5 (R507 scroll, 50 Hz, MT) CatalogCompressorsCopelandR507 compressor — 6.8 kW cooling, 2.70 kW input, COP 2.52 at -15/35 °C (evaporating/condensing), inside its published envelope.EU, APACOpen in the builder
Copeland ZF15K4E-TF5 (R507 scroll, 50 Hz, LL) CatalogCompressorsCopelandR507 compressor — 5.3 kW cooling, 2.48 kW input, COP 2.15 at -30/25 °C (evaporating/condensing), inside its published envelope.EU, APACOpen in the builder
Copeland YF32KAE-TFD (R455A scroll, 60 Hz, LL) CatalogCompressorsCopelandR455A compressor — 9.1 kW cooling, 6.38 kW input, COP 1.42 at -35/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland ZB29KCE-TF5 (R507 scroll, 60 Hz, MT) CatalogCompressorsCopelandR507 compressor — 8.1 kW cooling, 3.24 kW input, COP 2.52 at -15/35 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland ZF15K4E-TF5 (R507 scroll, 60 Hz, LL) CatalogCompressorsCopelandR507 compressor — 6.4 kW cooling, 2.98 kW input, COP 2.15 at -30/25 °C (evaporating/condensing), inside its published envelope.NAOpen in the builder
Copeland YF38KAE-TFD (R407F scroll, 50 Hz, LL) CatalogCompressorsCopelandR407F compressor — 9.3 kW cooling, 6.85 kW input, COP 1.35 at -35/35 °C (evaporating/condensing), inside its published envelope.EU, APACOpen in the builder
Copeland ZB29KCE-TF5 (R513A scroll, 50 Hz, HT) CatalogCompressorsCopelandR513A compressor — 7.1 kW cooling, 2.53 kW input, COP 2.79 at the AHRI 7.2/54.4 °C rating point.EU, APACOpen in the builder
Copeland ZF15KQE-TFC (R22 scroll, 50 Hz, LL) CatalogCompressorsCopelandR22 compressor — 3.5 kW cooling, 2.53 kW input, COP 1.39 at -35/30 °C (evaporating/condensing), inside its published envelope.APACOpen in the builder
‹ Previous1…622623624625626…643Next ›

Refrigerant circuit

Heat exchangers and recovery

Fans and air movement

Pumps and hydronics

Heating and humidity

Evaporative cooling and heat rejection

Cooling towers — none listed yet

Complete machines — air handlers, rooftops, splits, chillers, fan coils, cooling towers — are systems: the systems directory

Publishing here

Manufacturers publish from the supplier portal, or bulk-import a whole range over MCP. How it works for component vendors Twelve manufacturers' ranges are already in the catalog from their published data — the brands, and how to claim one