Recirculating gas rooftop, 3 m³/s

by HVAC Builder

Open this system in HVAC Builder Load it into the 3D builder, adjust it to your project, and solve it against your own climate — or drop it into a building model and simulate a full year.

The gas rooftop without its outside-air damper: a DX coil on a scroll, a gas furnace downstream of it for heat and reheat, a supply fan, a two-fan condenser — for a floor whose outside air comes from a dedicated unit. Published as an example; the figures below are solved from this model.

Example25–60 kW heating + coolingEU

Example system. Published by HVAC Builder to show suppliers what their own page looks like. There is no company behind it and it is not a product offer — the specification is generic and the performance is solved from the model on this page.

Design-point performance

56.5 kWcooling
16.3 kWelectrical power
3.47system COP

Solved from this example's own model each time the page loads — the same numbers a supplier's page shows for their machine.

Component schedule

ComponentKindDuty
DX coildxEvaporator56.5 kW
Gas furnace, 80 %heater0.0 kW
Supply fanfan-1.4 kW
Scroll compressors (4 × ZP49KHE)compressor12.5 kW
Air-cooled condensercondenser-68.4 kW
Condenser fans (2)fan-2.4 kW

Heat-pump rating

68.7 kWheating
15.8 kWelectrical power
4.35heating COP

Every air-coil refrigerant circuit here is reversible, so this machine is also a heat pump. Solved with the circuit running backwards at the standard air-to-air heating rating point — outdoor 7 °C dry bulb / 6 °C wet bulb, indoor 20 / 15 °C (EN 14511) — not at the supplier's own design conditions above, so the two ratings can be compared across machines.

Are you a manufacturer?

Publish your own range and this slot becomes your branded page — your data, your logo, your product link, and quote requests that reach you. Free to register and free to publish.

Open the Company page How it works