American Cooling Tower ACC-66C cooling tower (55 tons, 241 kW) — modelled
Modelled from the manufacturer's published data — not verified by American Cooling Tower. Source: American Cooling Tower ACC Series catalog, page 5 — the model's own row (nominal tons, fan motor HP, airflow in CFM, length and height) and the sheet's own note: nominal tons are 3 gpm cooled from 95 °F to 85 °F at a 78 °F wet bulb. Its second condition is the line's own CTI 49-point table, which the model reads at 0.12 K RMS over 538 points with the line's own fill-loading exponent (docs/american-cooling-tower-source.json). The figures below come from this model run against that data; the manufacturer has not reviewed them. Are you American Cooling Tower? Claim this page.
CTI STD-201 (validation C38E-25R00) ✓ verified — this model is named in the certification programme's own public register. It certifies the manufacturer's machine against their published ratings; it says nothing about the model of it that runs here, which is validated separately.
by HVAC Builder
Open this system in HVAC Builder Load it into the 3D builder, adjust it to your project, and solve it against your own climate — or drop it into a building model and simulate a full year.
American Cooling Tower's ACC-66C — an ACC cooling tower, 55 nominal tons (241 kW): rated to cool 165 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 9.0 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.
Example181–301 kW heat rejectionNAExample system. Published by HVAC Builder to show suppliers what their own page looks like. There is no company behind it and it is not a product offer — the specification is generic and the performance is solved from the model on this page.
Design-point performance
Solved from this example's own model as it is published — the same numbers a supplier's page shows for their machine.
Component schedule
| Component | Kind | Duty |
|---|---|---|
| ACC-66C fill | Wet pack | -238.8 kW |
| ACC-66C fan | Fan | -1.5 kW |
| ACC-66C tower-loop circulator | Pump | — |