American Cooling Tower ACC-86F cooling tower (108 tons, 473 kW) — modelled

Modelled from the manufacturer's published data — not verified by American Cooling Tower. Source: American Cooling Tower ACC Series catalog, page 5 — the model's own row (nominal tons, fan motor HP, airflow in CFM, length and height) and the sheet's own note: nominal tons are 3 gpm cooled from 95 °F to 85 °F at a 78 °F wet bulb. Its second condition is the line's own CTI 49-point table, which the model reads at 0.12 K RMS over 538 points with the line's own fill-loading exponent (docs/american-cooling-tower-source.json). The figures below come from this model run against that data; the manufacturer has not reviewed them. Are you American Cooling Tower? Claim this page.

CTI STD-201 (validation C38E-25R00) ✓ verified — this model is named in the certification programme's own public register. It certifies the manufacturer's machine against their published ratings; it says nothing about the model of it that runs here, which is validated separately.

by HVAC Builder

Open this system in HVAC Builder Load it into the 3D builder, adjust it to your project, and solve it against your own climate — or drop it into a building model and simulate a full year.

American Cooling Tower's ACC-86F — an ACC cooling tower, 108 nominal tons (473 kW): rated to cool 324 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 17.9 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by American Cooling Tower. Published as an example; the figures below are solved from this model.

Example355–591 kW heat rejectionNA

Example system. Published by HVAC Builder to show suppliers what their own page looks like. There is no company behind it and it is not a product offer — the specification is generic and the performance is solved from the model on this page.

Design-point performance

469.0 kWheat rejected
5.6 kWelectrical power
801 l/hwater use

Solved from this example's own model as it is published — the same numbers a supplier's page shows for their machine.

Component schedule

ComponentKindDuty
ACC-86F fillWet pack-469.0 kW
ACC-86F fanFan-5.6 kW
ACC-86F tower-loop circulatorPump—