Compressor — R410A compressor — 12.9 kW cooling, 5.19 kW input, COP 2.49 at the AHRI 7.2/54.4 °C rating point.
A Bitzer listing, from the manufacturer's published data.
| Model | BITZER 4FDC-5 (R410A recip, EN 12900) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 10.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 12.91 kW |
| Input power @ 7.2/54.4 °C | 5.19 kW |
| COP @ 7.2/54.4 °C | 2.49 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 10.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: not published — the map is used unbounded.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 10.38 | 3.15 | 3.29 |
| -10 / 40 | 8.79 | 3.59 | 2.45 |
| -10 / 60 | 5.33 | 4.11 | 1.30 |
| 0 / 30 | 15.21 | 3.30 | 4.61 |
| 0 / 40 | 13.08 | 3.98 | 3.29 |
| 0 / 60 | 8.38 | 5.01 | 1.67 |
| 10 / 30 | 21.51 | 3.14 | 6.86 |
| 10 / 40 | 18.71 | 4.10 | 4.56 |
| 10 / 60 | 12.49 | 5.72 | 2.18 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.