Compressor — R134a compressor — 1.0 kW cooling, 0.50 kW input, COP 1.98 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ARE35C5E-IAI (R134A hermetic recip, 60 Hz, HT) |
| Refrigerant | R134a |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 20.8 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 0.99 kW |
| Input power @ 7.2/54.4 °C | 0.50 kW |
| COP @ 7.2/54.4 °C | 1.98 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 20.8 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 40 | 0.61 | 0.31 | 1.99 |
| -10 / 50 | 0.52 | 0.33 | 1.59 |
| 0 / 40 | 0.94 | 0.38 | 2.47 |
| 0 / 50 | 0.81 | 0.41 | 1.97 |
| 0 / 60 | 0.67 | 0.45 | 1.50 |
| 10 / 40 | 1.39 | 0.48 | 2.93 |
| 10 / 50 | 1.22 | 0.51 | 2.37 |
| 10 / 60 | 1.02 | 0.56 | 1.81 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ARE35C5E-IAB (R513A hermetic recip, 50 Hz, HT) | R513A |
| compressors | Copeland ARE35C5E-CAA (R513A hermetic recip, 60 Hz, HT) | R513A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.