Catalog · Copeland

Copeland ARE46C4E-IAA (R513A hermetic recip, 60 Hz, HT)

Compressor — R513A compressor — 1.4 kW cooling, 0.85 kW input, COP 1.60 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ARE46C4E-IAA (R513A hermetic recip, 60 Hz, HT)
RefrigerantR513A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool20.8 / 0.0 K
Cooling capacity @ 7.2/54.4 °C1.37 kW
Input power @ 7.2/54.4 °C0.85 kW
COP @ 7.2/54.4 °C1.60

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 20.8 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 400.890.541.64
-10 / 500.770.581.32
0 / 401.340.662.04
0 / 501.130.711.59
0 / 600.950.761.25
10 / 401.900.842.25
10 / 501.630.891.84
10 / 601.350.931.45

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy