Catalog · Copeland

Copeland ZB114KCE-TFD (R507 scroll, 60 Hz, MT)

Compressor — R507 compressor with a 10-coefficient AHRI 540 map.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZB114KCE-TFD (R507 scroll, 60 Hz, MT)
RefrigerantR507
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.5 / 0.0 K

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.5 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 1034.607.674.51
-20 / 3027.6011.122.48
-10 / 1050.447.886.40
-10 / 3040.3911.943.38
-10 / 6023.5319.651.20
0 / 3057.5912.234.71
0 / 6033.0820.921.58

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZB114KCE-TFD (R134A scroll, 50 Hz, HT)R134a
compressorsCopeland ZB114KCE-TFD (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland ZB114KCE-TED (R22 scroll, 50 Hz, HT)R22
compressorsCopeland ZB114KCE-TED (R22 scroll, 60 Hz, HT)R22
compressorsCopeland ZB114KCE-TFD (R404A scroll, 50 Hz, MT)R404A
compressorsCopeland ZB114KCE-TFD (R404A scroll, 60 Hz, MT)R404A
compressorsCopeland ZB114KCE-TFD (R407C scroll, 50 Hz, HT)R407C
compressorsCopeland ZB114KCE-TFD (R407C scroll, 60 Hz, HT)R407C
compressorsCopeland ZB114KCE-TFD (R507 scroll, 50 Hz, MT)R507

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy