Catalog · Copeland

Copeland ZB95K5E-TFD (R134A scroll, 50 Hz, HT)

Compressor — R134a compressor — 22.9 kW cooling, 7.85 kW input, COP 2.92 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZB95K5E-TFD (R134A scroll, 50 Hz, HT)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 0.0 K
Cooling capacity @ 7.2/54.4 °C22.91 kW
Input power @ 7.2/54.4 °C7.85 kW
COP @ 7.2/54.4 °C2.92

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-10 / 3015.004.503.33
-10 / 5011.296.901.64
0 / 3022.944.684.90
0 / 5018.167.032.58
0 / 7011.8510.941.08
10 / 3033.804.956.82
10 / 5027.227.233.77
10 / 7019.4211.111.75

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZB95K5E-TFD (R134A scroll, 60 Hz, HT)R134a
compressorsCopeland ZB95K5E-TFD (R404A scroll, 50 Hz, MT)R404A
compressorsCopeland ZB95K5E-TFE (R404A scroll, 60 Hz, MT)R404A
compressorsCopeland ZB95K5E-TFD (R448A scroll, 50 Hz, MT)R448A
compressorsCopeland ZB95K5E-TFD (R448A scroll, 60 Hz, MT)R448A
compressorsCopeland ZB95K5E-TFD (R513A scroll, 50 Hz, HT)R513A
compressorsCopeland ZB95K5E-TFD (R513A scroll, 60 Hz, HT)R513A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy