Compressor — R513A compressor — 23.3 kW cooling, 8.24 kW input, COP 2.83 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZB95K5E-TFD (R513A scroll, 50 Hz, HT) |
| Refrigerant | R513A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 18.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 23.29 kW |
| Input power @ 7.2/54.4 °C | 8.24 kW |
| COP @ 7.2/54.4 °C | 2.83 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 18.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 6-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 30 | 16.49 | 4.76 | 3.47 |
| -10 / 50 | 12.74 | 7.20 | 1.77 |
| 0 / 30 | 24.42 | 5.06 | 4.82 |
| 0 / 50 | 19.14 | 7.41 | 2.58 |
| 0 / 70 | 13.14 | 11.06 | 1.19 |
| 10 / 30 | 34.91 | 5.49 | 6.36 |
| 10 / 50 | 27.45 | 7.65 | 3.59 |
| 10 / 70 | 19.05 | 11.18 | 1.70 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZB95K5E-TFD (R134A scroll, 50 Hz, HT) | R134a |
| compressors | Copeland ZB95K5E-TFD (R134A scroll, 60 Hz, HT) | R134a |
| compressors | Copeland ZB95K5E-TFD (R404A scroll, 50 Hz, MT) | R404A |
| compressors | Copeland ZB95K5E-TFE (R404A scroll, 60 Hz, MT) | R404A |
| compressors | Copeland ZB95K5E-TFD (R448A scroll, 50 Hz, MT) | R448A |
| compressors | Copeland ZB95K5E-TFD (R448A scroll, 60 Hz, MT) | R448A |
| compressors | Copeland ZB95K5E-TFD (R513A scroll, 60 Hz, HT) | R513A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.