Compressor — R410A compressor — 29.0 kW cooling, 10.62 kW input, COP 2.74 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZP137KZE-TFD (R410A scroll, 50 Hz, AC) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 29.04 kW |
| Input power @ 7.2/54.4 °C | 10.62 kW |
| COP @ 7.2/54.4 °C | 2.74 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 9-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 19.01 | 3.84 | 4.96 |
| -20 / 30 | 15.04 | 6.19 | 2.43 |
| -10 / 10 | 28.37 | 3.62 | 7.85 |
| -10 / 30 | 23.72 | 6.08 | 3.90 |
| 0 / 30 | 34.79 | 5.87 | 5.93 |
| 0 / 60 | 21.01 | 12.80 | 1.64 |
| 20 / 60 | 46.47 | 11.77 | 3.95 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZP137KZE-TFD (R410A scroll, 60 Hz, AC) | R410A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.