Catalog · Copeland

Copeland ZP154KPE-TFD (R410A scroll, 60 Hz, AC)

Compressor — R410A compressor — 40.4 kW cooling, 14.24 kW input, COP 2.84 at the AHRI 7.2/54.4 °C rating point.

A Copeland listing, from the manufacturer's published data.

Published specification

ModelCopeland ZP154KPE-TFD (R410A scroll, 60 Hz, AC)
RefrigerantR410A
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool11.1 / 0.0 K
Cooling capacity @ 7.2/54.4 °C40.36 kW
Input power @ 7.2/54.4 °C14.24 kW
COP @ 7.2/54.4 °C2.84

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-20 / 3019.768.422.35
-20 / 4016.7210.301.62
-10 / 3030.358.303.66
-10 / 4026.8210.472.56
0 / 3043.828.285.29
0 / 4039.2910.253.83
0 / 6027.3016.471.66
10 / 3061.179.116.72
10 / 4055.1410.365.32
10 / 6039.7316.222.45

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsCopeland ZP154KPE-TFD (R410A scroll, 50 Hz, AC)R410A

How the model reads against this maker's data

Compressor maps converted from the vendor's own rating database4 776 mapsevery basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy