Compressor — R410A compressor — 33.0 kW cooling, 11.89 kW input, COP 2.78 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZP154KZE-TF5 (R410A scroll, 50 Hz, AC) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 33.05 kW |
| Input power @ 7.2/54.4 °C | 11.89 kW |
| COP @ 7.2/54.4 °C | 2.78 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 9-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 21.55 | 4.02 | 5.36 |
| -20 / 30 | 17.81 | 6.69 | 2.66 |
| -10 / 10 | 31.83 | 3.87 | 8.22 |
| -10 / 30 | 27.04 | 6.67 | 4.05 |
| 0 / 30 | 39.02 | 6.53 | 5.98 |
| 0 / 60 | 25.00 | 13.94 | 1.79 |
| 20 / 60 | 52.16 | 13.36 | 3.90 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZP154KZE-TFE (R410A scroll, 60 Hz, AC) | R410A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.