Compressor — R410A compressor — 61.5 kW cooling, 21.22 kW input, COP 2.90 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZP236KCE-TE5 (R410A scroll, 60 Hz, AC) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 61.53 kW |
| Input power @ 7.2/54.4 °C | 21.22 kW |
| COP @ 7.2/54.4 °C | 2.90 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 8-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 10 | 40.45 | 8.73 | 4.63 |
| -20 / 30 | 31.47 | 12.34 | 2.55 |
| -10 / 10 | 60.47 | 9.16 | 6.60 |
| -10 / 30 | 48.74 | 12.66 | 3.85 |
| 0 / 30 | 71.87 | 13.22 | 5.44 |
| 0 / 60 | 48.48 | 23.50 | 2.06 |
| 20 / 60 | 98.73 | 24.81 | 3.98 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZP236KCE-TE5 (R410A scroll, 50 Hz, AC) | R410A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.