Compressor — R410A compressor — 7.0 kW cooling, 2.65 kW input, COP 2.65 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZP27KHE-PFB (R410A scroll, 60 Hz, AC) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 8.3 K |
| Cooling capacity @ 7.2/54.4 °C | 7.03 kW |
| Input power @ 7.2/54.4 °C | 2.65 kW |
| COP @ 7.2/54.4 °C | 2.65 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 8.3 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 3.37 | 1.55 | 2.18 |
| -20 / 40 | 2.65 | 1.91 | 1.38 |
| -10 / 30 | 5.42 | 1.54 | 3.52 |
| -10 / 40 | 4.70 | 1.92 | 2.45 |
| 0 / 30 | 7.95 | 1.50 | 5.30 |
| 0 / 40 | 7.10 | 1.90 | 3.74 |
| 0 / 60 | 5.46 | 3.07 | 1.78 |
| 10 / 30 | 11.31 | 1.43 | 7.89 |
| 10 / 40 | 10.19 | 1.85 | 5.52 |
| 10 / 60 | 8.14 | 3.02 | 2.69 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.