Compressor — R410A compressor — 75.6 kW cooling, 28.08 kW input, COP 2.69 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZP296KWE-TE5 (R410A scroll, 60 Hz, WC) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 5.6 K |
| Cooling capacity @ 7.2/54.4 °C | 75.57 kW |
| Input power @ 7.2/54.4 °C | 28.08 kW |
| COP @ 7.2/54.4 °C | 2.69 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 5.6 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -18 to 18 °C, condensing 9 to 49 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 10 | 72.16 | 9.28 | 7.77 |
| -10 / 20 | 66.04 | 12.31 | 5.37 |
| -10 / 40 | 52.69 | 21.06 | 2.50 |
| 0 / 10 | 104.45 | 8.43 | 12.40 |
| 0 / 20 | 95.93 | 11.41 | 8.41 |
| 0 / 40 | 77.91 | 19.88 | 3.92 |
| 10 / 20 | 135.07 | 10.46 | 12.91 |
| 10 / 40 | 110.79 | 18.54 | 5.97 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.