Compressor — R410A compressor — 82.6 kW cooling, 28.50 kW input, COP 2.90 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZP385KPE-TWD (R410A scroll, 50 Hz, AC) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 82.58 kW |
| Input power @ 7.2/54.4 °C | 28.50 kW |
| COP @ 7.2/54.4 °C | 2.90 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 42.11 | 16.16 | 2.61 |
| -20 / 40 | 36.70 | 20.40 | 1.80 |
| -10 / 30 | 62.90 | 16.37 | 3.84 |
| -10 / 40 | 55.61 | 20.48 | 2.71 |
| 0 / 30 | 90.63 | 16.76 | 5.41 |
| 0 / 40 | 80.82 | 20.61 | 3.92 |
| 0 / 60 | 55.84 | 32.66 | 1.71 |
| 10 / 30 | 126.76 | 17.60 | 7.20 |
| 10 / 40 | 113.80 | 21.06 | 5.40 |
| 10 / 60 | 81.16 | 32.38 | 2.51 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Copeland ZP385KPE-TWD (R410A scroll, 60 Hz, AC) | R410A |
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.