Compressor — R410A compressor — 97.8 kW cooling, 38.03 kW input, COP 2.57 at the AHRI 7.2/54.4 °C rating point.
A Copeland listing, from the manufacturer's published data.
| Model | Copeland ZP485KWE-DE5 (R410A scroll, 50 Hz, WC) |
| Refrigerant | R410A |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 11.1 / 5.6 K |
| Cooling capacity @ 7.2/54.4 °C | 97.83 kW |
| Input power @ 7.2/54.4 °C | 38.03 kW |
| COP @ 7.2/54.4 °C | 2.57 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 11.1 K superheat and 5.6 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -18 to 18 °C, condensing 9 to 49 °C (a rectangle). The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -10 / 10 | 99.33 | 12.32 | 8.06 |
| -10 / 20 | 90.44 | 16.38 | 5.52 |
| -10 / 40 | 69.15 | 28.15 | 2.46 |
| 0 / 10 | 138.66 | 11.57 | 11.99 |
| 0 / 20 | 130.42 | 15.50 | 8.41 |
| 0 / 40 | 104.15 | 26.81 | 3.88 |
| 10 / 20 | 178.63 | 14.50 | 12.32 |
| 10 / 40 | 150.28 | 25.18 | 5.97 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| Compressor maps converted from the vendor's own rating database | 4 776 maps | every basis median within 3.2 % of the nomenclature; the vendor's polynomial substituted exactly, never refitted |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.