Embraco EM2P60CLP (R600a hermetic, LBP, EN12900, 60 Hz)
Compressor — R600a compressor — 0.13 kW cooling, 0.10 kW input, COP 1.30 at -30/40 °C (evaporating/condensing), inside its published envelope.
An Embraco listing, from the manufacturer's published data.
Units: SI · US customary
Published specification
| Model | Embraco EM2P60CLP (R600a hermetic, LBP, EN12900, 60 Hz) |
| Refrigerant | R600a |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 42.5 / 0.0 K |
| Cooling capacity @ -30/40 °C | 0.13 kW |
| Input power @ -30/40 °C | 0.10 kW |
| COP @ -30/40 °C | 1.30 |
The map across its envelope
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 42.5 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -30 / 40 | 0.13 | 0.10 | 1.30 |
| -25 / 40 | 0.17 | 0.11 | 1.48 |
| -15 / 40 | 0.27 | 0.14 | 1.92 |
Conditions across the published envelope, which does not reach the AHRI air-conditioning rating point (7.2/54.4 °C) — the map is not read there. The whole map — every condition, the envelope and the curves — is in the builder: open this machine in the app. It solves any point inside the envelope, and warns past it.
Open this compressor in the app — the compressor-map tab, with its rating at any condition, its envelope, capacity and power lines and curves plotted, and the refrigerant's pressure–temperature chart a click away; or open the builder and pick it from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
How the model reads against this maker's data
| Embraco hermetic and variable-capacity compressor maps, fitted from the maker's published tables | 1 283 maps from 815 models (R134a 518, R600a 315, R290 285, R404A 141, R22 11, R1234yf 10, R422D 2, R502 1); 178 variable-capacity models with a table per speed | fitted at the order each table's levels determine (three condensing levels: quadratic in tc), the tables are reproduced at a median RMS of 0.08 % (p90 0.20 %); every map reads the standard's own rating point within 0.08 % at the median and 0.4 % at the ninetieth percentile; every carried flow set closes the identity once the rating's own return-gas and liquid temperatures are read off the node (ASHRAE rates with the liquid at 32.2 °C, 22 K under the condenser). 72 tables withheld and listed by reason: blend groups published as one table, variable-capacity models with fewer than three speeds tabulated, three with a COP under 0.5 at the rating point, three duplicates |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.