Catalog · Embraco

Embraco FF10HBK (R134a hermetic, HBP, EN12900, 60 Hz)

Compressor — R134a compressor — 0.8 kW cooling, 0.46 kW input, COP 1.80 at the AHRI 7.2/54.4 °C rating point.

A Embraco listing, from the manufacturer's published data.

Published specification

ModelEmbraco FF10HBK (R134a hermetic, HBP, EN12900, 60 Hz)
RefrigerantR134a
Performance dataAHRI 540 / EN 12900 10-coefficient map
Reference superheat / subcool30.0 / 0.0 K
Cooling capacity @ 7.2/54.4 °C0.83 kW
Input power @ 7.2/54.4 °C0.46 kW
COP @ 7.2/54.4 °C1.80

The map across its envelope

AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 30.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: the manufacturer's 5-sided polygon. The mass-flow coefficient set is published too, and the solver checks it against the capacity set.

te / tc °CCapacity kWPower kWCOP
-30 / 200.250.161.58
-30 / 400.170.180.94
-30 / 600.100.180.58
-20 / 200.420.192.22
-20 / 400.310.241.29
-20 / 600.200.240.83
-10 / 200.670.213.22
-10 / 400.510.301.69
-10 / 600.350.331.07
10 / 201.410.1310.60
10 / 401.130.373.06
10 / 600.840.511.65

Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.

Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.

Same family

compressorsEmbraco FF10HBK (R134a hermetic, MBP, EN12900, 60 Hz)R134a
compressorsEmbraco FF10HBK (R134a hermetic, LBP, ASHRAE, 60 Hz)R134a

How the model reads against this maker's data

Embraco hermetic and variable-capacity compressor maps, fitted from the maker's published tables1,283 maps from 815 models (R134a 518, R600a 315, R290 285, R404A 141, R22 11, R1234yf 10, R422D 2, R502 1); 178 variable-capacity models with a table per speedfitted at the order each table's levels determine (three condensing levels: quadratic in tc), the tables are reproduced at a median RMS of 0.08 % (p90 0.20 %); every map reads the standard's own rating point within 0.08 % at the median and 0.4 % at the ninetieth percentile; every carried flow set closes the identity once the rating's own return-gas and liquid temperatures are read off the node (ASHRAE rates with the liquid at 32.2 °C, 22 K under the condenser). 72 tables withheld and listed by reason: blend groups published as one table, variable-capacity models with fewer than three speeds tabulated, three with a COP under 0.5 at the rating point, three duplicates

From the validation page; every row is held by a test.

Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy