EVAPCO AT 212-3K24 cooling tower (804 tons, 3.5 MW) — modelled

Modelled from the manufacturer's published data — not verified by EVAPCO. Source: EVAPCO AT Engineering Data & Dimensions — the model's own row (nominal tonnage, airflow in CFM, fan motor and its printed count, height and length) and the sheet's own note: nominal tonnage is 3 gpm per ton at 95 °F entering water, 85 °F leaving and a 78 °F wet bulb. Its second condition is EVAPCO's own CTI 49-point table, which the model reads at 0.22 K RMS over 45 945 points (docs/evapco-cti-source.json). The figures below come from this model run against that data; the manufacturer has not reviewed them. Are you EVAPCO? Claim this page.

CTI STD-201 (validation C13A-99R28) ✓ verified — this model is named in the certification programme's own public register. It certifies the manufacturer's machine against their published ratings; it says nothing about the model of it that runs here, which is validated separately.

by HVAC Builder

Open this system in HVAC Builder Load it into the 3D builder, adjust it to your project, and solve it against your own climate — or drop it into a building model and simulate a full year.

EVAPCO's 212-3K24 — a AT cooling tower, 804 nominal tons (3536 kW): rated to cool 2421 USGPM of water from 95 to 85 °F at a 78 °F entering wet bulb on 82.6 m³/s of air, the maker's own printed airflow, and drawn at those flows with an induced-draft fan on the leaving air, pulling through the fill. Open fill: the water meets the air directly — Braun's enthalpy-basis tower model. The model derives the machine's NTU from that one certified point, so it reproduces the rated leaving water exactly and predicts nothing else — one point per model is an input, not a validation. Modelled from the manufacturer's published data — not verified by EVAPCO. Published as an example; the figures below are solved from this model.

Example2652–4420 kW coolingEU

Example system. Published by HVAC Builder to show suppliers what their own page looks like. There is no company behind it and it is not a product offer — the specification is generic and the performance is solved from the model on this page.

Design-point performance

3493.5 kWcooling
29.8 kWelectrical power
5211 l/hwater use
117.12system COP

Solved from this example's own model each time the page loads — the same numbers a supplier's page shows for their machine.

Component schedule

ComponentKindDuty
212-3K24 fillwetPack-3493.5 kW
212-3K24 fanfan-29.8 kW
212-3K24 tower-loop circulatorpump—