Compressor — R22 compressor — 12.9 kW cooling, 5.40 kW input, COP 2.38 at the AHRI 7.2/54.4 °C rating point.
A Tecumseh listing, from the manufacturer's published data.
| Model | Tecumseh AGB4561ZKZ (R22 hermetic, HBP, EN12900, 50 Hz) |
| Refrigerant | R22 |
| Performance data | AHRI 540 / EN 12900 10-coefficient map |
| Reference superheat / subcool | 25.0 / 0.0 K |
| Cooling capacity @ 7.2/54.4 °C | 12.89 kW |
| Input power @ 7.2/54.4 °C | 5.40 kW |
| COP @ 7.2/54.4 °C | 2.38 |
AHRI 540 / EN 12900 ten-coefficient polynomials in evaporating and condensing temperature, rated at 25.0 K superheat and 0.0 K subcooling; the solver corrects them to the operating superheat and subcooling. Envelope: evaporating -25 to 15 °C, condensing 30 to 60 °C (a rectangle).
| te / tc °C | Capacity kW | Power kW | COP |
|---|---|---|---|
| -20 / 30 | 5.36 | 2.54 | 2.11 |
| -20 / 40 | 4.37 | 2.53 | 1.73 |
| -20 / 60 | 2.15 | 2.62 | 0.82 |
| -10 / 30 | 9.09 | 3.06 | 2.97 |
| -10 / 40 | 7.68 | 3.27 | 2.35 |
| -10 / 60 | 4.85 | 3.79 | 1.28 |
| 0 / 30 | 14.37 | 3.58 | 4.01 |
| 0 / 40 | 12.27 | 4.00 | 3.07 |
| 0 / 60 | 8.33 | 4.94 | 1.68 |
| 10 / 30 | 21.56 | 4.12 | 5.24 |
| 10 / 40 | 18.53 | 4.74 | 3.91 |
| 10 / 60 | 12.96 | 6.08 | 2.13 |
Points on a 10 K grid inside the published envelope; the builder solves any point in it, and warns past it.
Open the builder and pick this listing from the catalog picker — the solver runs it with the catalog's own figures, at your design point or across a year of weather.
| compressors | Tecumseh AGB4561ZKZ (R22 hermetic, HBP, EN12900, 60 Hz) | R22 |
| compressors | Tecumseh AGB4561ZKZ (R404A hermetic, HBP, EN12900, 50 Hz) | R404A |
| compressors | Tecumseh AGB4561ZKZ (R404A hermetic, HBP, EN12900, 60 Hz) | R404A |
| Tecumseh hermetic compressor maps, the maker's own coefficient sets | 864 maps from 297 models (R404A 324, R134a 178, R290 109, R22 97, R513A 89, R1234yf 53, R600a 10, R410A 4) at 93 application × refrigerant × frequency listings | power reads the selector's point within 0.95 % on every map (units and coefficient order, BTU/h sets scaled and Fahrenheit sets substituted exactly); 522 maps rate at their own basis and read the selector's capacity within 1 %; on the 342 the selector corrected from a liquid-temperature or return-gas basis to the regime, this solver's AHRI 540 §6 correction reproduces the selector's corrected capacity within +0.3 % on average (the raw polynomial sits +9.5 % over it), single maps ±11 % where a return-gas basis is carried as one reference superheat. 2 028 zeotrope rows (R448A, R449A, R452A, R454C, R455A, R407C) are withheld: Tecumseh publishes them on the glide's mid-point where AHRI 540 and this catalog rate on dew points |
From the validation page; every row is held by a test.
Listed from published data; a listing's figures are the manufacturer's, the model that runs them is ours. Solver results never depend on who has claimed what.