What is head-pressure control?

Head-pressure control. Condenser fans taken off on a cool day to hold a minimum condensing temperature — a constraint an expansion valve needs, not an economy. Head-pressure control.

On a cold day an air-cooled condenser rejects heat too well: the condensing pressure falls, the expansion valve loses the pressure difference it meters on, and the circuit starves. Head-pressure control holds the condensing temperature at a floor by taking condenser air away — fan cycling, a fan bank staged down, or a speed-controlled fan — the least air that keeps the head where the valve needs it.

It is a constraint, not an economy: at full output the staged point draws more than the free-floating one, because a higher condensing temperature costs compressor power. HVAC Builder settles the head before a stage is judged, walking the fan bank's ladder down until the running condensing temperature reaches the setpoint, and re-settles it at the part load the machine actually runs at.

Open the builder — the examples in the Design tab's sources list include a machine of this kind, and the Simulate tab runs it against a year of weather.

Other terms

DOAS — dedicated outside-air system · SZVAV — single-zone variable air volume · VAV terminal box · Economiser · Waterside economiser · Demand-controlled ventilation · Face-and-bypass · Humidity ceiling and floor · Cycling and modulation · Coupling · Priority · Category · Nested system · Design point and TMY year

HVAC Builder · engineering results are estimates from catalog data and published correlations: ASHRAE, IAPWS-IF97, AHRI 540, EnergyPlus, CoolProp · weather data: PVGIS © European Union, JRC · contact: leads@hvacbuilder.app · bugs: bugs@hvacbuilder.app · validation · changelog · manufacturers · catalog · tools · Systems · Components · Suppliers · Privacy